Water Leak Detection System – WLDS-20 mk3 Major Leak Detector
If the flow rate exceeds preset parameters an alarm sounds and optionally the water supply can be shut off.
WLDS water leak detection systems activate when the flow of water exceeds the preset maximum for the preset period. It identifies different flows and therefore leakage rates, in accordance with BREEAM WAT03. This gives you flexibility to adjust the parameters to suit your specific conditions.
Features
- Easy to navigate user interface
- Accepts inputs from 1, 5, 10 or 100 LPP reed switch type pulse meters
- Main (M1) & Sub (M2) pulse meters can have different K factors (number of pulses produced per gallon of water)
- Seven-day clock enables different periods of high flow (HF) to be programmed
- Peak flow capture enables easy setting of accurate parameters
- Displays total throughput in litres – useful for parameter setting and water audits
- Output contact for BMS or optional SB-100 sounder/beacon alarm
- Output for 24v DC Normally Closed or Normally Open solenoid valve with timed service function
- Solenoid valve set up enables a Normally Closed or a Normally Open solenoid valve to be selected in software
- Timed valve service function can be set to reduce the likelihood of valve sticking due to calcification etc.
- Manual override (protection off) function with adjustable timeout period
- External alarm input for the connection of ancillary equipment such as tape leak sensing to be interfaced to the water leak detection system
- Enclosure 300 x 300 x 150mm with a RH hinged door. Facilitates easier wall mounting and access to the internal terminals
- Alarm test function
- Tough steel wall mounting enclosure to IP65 protection, optional wall mounting brackets WMB-100
- Universal 100-240v 50/60Hz input for worldwide use
- Designed and manufactured in the UK
Power requirements | Universal input 100-260v AC 50/60Hz 1.5A max |
Pulse meter input | 24v DC 5mA maximum for reed switch type pulse meter, programmable for 1, 5, 10 or 100 litres per pulse |
PSU output | 24v DC @ 1.1A for powering alarm or solenoid valves |
Alarm output | Normally open free relay contact rated at 5A resistive load 250v AC / 30v DC |
Valve output | Free relay contact rated at 5A resistive load 250v AC / 30v DC, programmable as Normally Open or Normally Closed with timed service function |
Additional outputs | Two alarm contacts are available |
External HF/LF input | Overrides internal clock |
External alarm input | Enable ancillary equipment such as tape sensing to be interfaced to the WLDS-10/20 mk3 panels |
LCD display | 2x 16 ASCII character with LED backlight |
Keypad | With tactile feedback 0-9 numeric keys plus navigation keys for parameter setting and monitoring |
Parameters | Litres input range 1-32,767, time input range 1 minute – 45 hours, number of High Alerts to alarm: 1-99 |
Real-time clock | Displaying day and time (24hr format) with automatic GMT/BST changeover. Incudes battery. |
Connections | DIN rail terminals, maximum conductor size 4mm², cable entry via IP65 cable gland in gland plate |
Enclosure | IP65, steel wall mounting overall dimensions 300x300x150mm (WxHxD) RAL7035 powder coated |
Weight | Approximately 6kg |